Upload Siemens Parameters G120-S120 using Starter Software

Dear PLC Technical members,

Welcome to our followers on the Blog PLC Technical, this article explains how to upload the drive parameter of the Siemens G120/S120 drive. Siemens starter software is used to upload and configuration of the drive. Sinamics G120/S120 drive is the best arrangement of a drive from Siemens. So this article can help to upload the parameter of drive.

UPLOAD SIEMENS PARAMETERS G120S120 USING STARTER SOFTWARE

I. Upload Siemens Parameters G120-S120 using Starter Software

I will show you how to establish a communication with the module CUS (control-unit) and load its parameter with the Siemens development Starter software via Ethernet.
  • Select a new project in a new folder
  • Select set PG/PC protocol
  • Select accessible node Select drive node for upload
  • Connect and upload the drive parameter to PG
  • Drive parameter upload successfully
  • See drive parameter online
Please check this link:
Construction of Sinamics Siemens S120

1. STARTER by means of Ethernet câble:

The Control Unit can be appointed with the PG/PC using the incorporated Ethernet interface.

Precondition:
  • STARTER software as of version 4.1.5
  • Control Unit CU320-2 PN
  • Connecting the PG/PC to the Control Unit CU320 via Ethernet

Connecting the PGPC to the Drive CU320 via Ethernet


Setting the IP address in Windows 7, The following procedure is based on the Windows 7 operating system.

  1. In the control board of your PG/PC, under "System and Internet", select the "System and Sharing Center" work.
  2. For your system card that is shown, click the associated interface.
  3. Snap-in the status exchange of the association on "Properties" and recognize the ensuing affirmation brief with "Yes".
  4. In the property exchange of the association, select the "Internet Protocol 4 (TCP/IPv4)" component and afterward click "Properties"
  5. In the property exchange, actuate the "Utilization the accompanying IP address" choice.
  6. Set the IP address of the PG/PC to get to interface to the Control Unit to 169.254.11.1 and the subnet cover to 255.255.0.0.

2. Commissioning tool of the STARTER

In the STARTER commissioning tool, set the communication using Ethernet cable as follows (in our model, we are utilizing the Ethernet interface )

2.1 Create a new project:

Select a new project in a new folder: Enter the following project data
  • Project name: Project_1, can be freely selected
  • Author: Any
  • Storage location: Any
  • Comment: Any
  • Click "Continue >" or "next >"

2.2  Choosing the access point:

The target device can be gotten to utilizing S7ONLINE STEP 7 or through device STARTER Select the access point for the open hubs, and affirm with "alright" or "ok"

2.3  Choosing the PG/PC interface:

Select the menu "Devices > Set PG/PC interface:

  • The PG interface can be arranged in this window. There are two choices (Access point and PG/PC)
  • Click "PG/PC"
  • Select the access path. Then select the TCP/IP protocol for the network board used. Click "Properties".
  • Select the IP address option in the Properties dialog box. And the interface TCP/IP S7ONLINE (STEP7) -> Intel (R) 82579LM Gigabit Network Connection. TCP IP.1
  • Click "OK" to confirm your settings.

2.4  Select Accessible node for upload

Select the menu "Project > Accessible nodes" or click the image "Accessible nodes" to search for available nodes in the Ethernet.

2.5  Connect and upload drive parameter to PG

To load the parameters Siemens G120 to the drive unit, proceed as follows:
  • Open the project drive unit by choosing Project > Open.
  • To utilize the “control panel” function, you need to change to ONLINE mode. To change to ONLINE mode, click the capacity key Connect to the target system.
  • On the ONLINE/OFFLINE correlation is completed.
  • Click Load HW configuration to PG in the “ONLINE/OFFLINE comparison”
  • Click load project to PG: all parameters from drive to the laptop.
  • Click Yes. The system now starts loading the data.

2.6  Drive parameter upload successfully

At the point when the framework illuminates you that the information was effectively loaded to the target framework, click OK.


From here we have finished the subject of the Upload Siemens Parameters G120-S120 using Starter Software, if you like it, please share it with friends until it benefits, and then meet on a new topic on blog PLC Technical. 

Regards,
PLC Technical

Post a Comment

Post a Comment (0)