Dear PLC Technical members,
Welcome to our follow-up on today's PLC Technicals blog, we will start together in the second lesson of the course SIMATIC HMI TP700 Comfort.
This article provides a step-by-step example of how to backup an HMI runtime project from a SIMATIC HMI TP700 Comfort, and how to subsequently restore an HMI runtime project to a SIMATIC HMI TP700 Comfort via Ethernet, using the ProSave utility.
This allows the user to quickly load multiple HMI runtime projects to identify devices without the requirement for any WinCC programming.
I. Backing up and restoring a program HMI TP700 comfort via Prosave
- Automatic backup
- Backup the Program with a memory card/USB
- Backup the Program with a software Pro save
Today At this point we will touch upon Backup Program of the SIMATIC HMI TP700 Comfort via Pro Save
1. Fundamentals the Backup Program TP700 Comfort with Prosave
- First, we have to connect Ethernet cable to SIMATIC HMI TP700 Comfort and PC.
- Power cycle (turn off and on) the SIMATIC HMI TP700 Comfort by pulling out and reattaching the green plug on the back of the TP700 Comfort panel.
- We will Power on SIMATIC HMI TP700 Comfort to boot up
- Go to the setting menu and set transfer function for Ethernet
- Run Pro save and select the SIMATIC HMI model TP700 and Ethernet as
- transfer channel Transferred successfully...
2. Power cycle (turn off and on) the SIMATIC HMI TP700 Comfort by pulling out and reattaching the green plug on the back of the TP700 Comfort panel. Know to go to following stage whit in 3 seconds.
3. Power on the power supply, the display lights up. After starting the operating system, the desktop displays SIMATIC HMI TP700 Comfort with the Start Center.
4. Go To the setting menu control panel and set transfer function for ethernet
1.1 Proceed as follows:
- Open the Transfer icon
- you should indicate the Transfer mode via Ethernet in the menu Transfer Settings.At the point when you select the "Ethernet" choice, you should show the IP address
- Open the network adapter display via the "SOC1 Ethernet Driver Settings"
- The "SOC1 Ethernet Driver Settings" dialog box opens.
- Activate the "IP Address"
- Choose the type of address assignment
- To determine the address manually, enable "Specify an IP address".192.1.6.44
- Confirm the section by "OK"
- we will run Software Prosave,select the SIMATIC HMI model TP700 Comfort and Ethernet as Transfer channel, and insert the IP address 192.1.6.44 of the Device
- Select the Backup and picked an area for the reinforcement by tapping the "… " catch and press the “Start backup”.
- Select the Restore tab and picked the area of the reinforcement record to be by tapping the "… " catch and press the "Start reestablish"
- Open the "Restore" menu. Below Open, you open (name of your project.brf). Start the restore framework by tapping the "Start Restore" button.
The following figure shows the open Control Panel
1.2 Backup:
The first commissioning, the operator console automatically switches to the "Transfer". Now click the Transfer button it will wait for the PC and Simatic HMI TP700 comfort to connect.
Select the Backup tab and picked an area for the reinforcement by tapping the "… " catch and press the “Start backup”. Way of naming the backup file is as follows: TP700 Comfort. Brf
Backup TP700 was created successfully
In this Article, we will see the steps for transferring the Simatic HMI TP700 Program on the touch panel to the USB memory.
1.3 Restore:
To start with, you execute the "Arrangement" as depicted previously.- Power on the panel
- Connect a standard Ethernet cable between the PC and the SIMATIC HMI TP700 Comfort either directly or via a switch/hub.
- Open the ProSafe Software
- Select the relating Device under "Device type" and supplement the IP address (192.1.6.44) of the Device
- Select the Restore tab and picked the area of the reinforcement record to be by tapping the "… " catch and press the "Start reestablish"
- Open the "Restore" menu. Below Open , you open (name of your project.brf). Start the restore framework by tapping the "Start Restore" button.
Once the restore methodology is finished, the "restore was successful" message is shown in the Pro save yield window.
From here we have finished the subject of the Backing up and restoring a program, Simatic HMI TP700 comfort via Pro save, if you like it, please share it with friends until it benefits, and then meet on a new topic on blog PLC Technical.
Regards,
PLC Technical